Office     (04) 499-0010
 Fax        (04) 499-0040

 sales@csinz.com

Honeywell - Temperature Compensator Optimiser - Aquatrol 2000

 

Versatile Outside Temp Compensation controller for central heating and domestic hot water installations. Sequence control of 2 boilers or 2-stage burner, mixing valve + heating pump control, domestic hot water pump.

Power source

230V +10%, -15% 50 Hz, 8W

Control output signal

potential free relays rated: 3A, 230 V AC for pumps and burners, 0,25 A 230 V AC for mixing valve

Control functions

boiler temperature control, supply water temperature control with outside temperature compensation, domestic hot water control

Modes of operations

auto, summer, holiday, off, start up, service

Applicable sensor types

NTC 10kOhm

Clock functions

digital clock with weekly program for heating and hot water

LED functions

indicating LED's for every relay output

Protection class

IP30

Memory back up

Super-cap for the time settings/EEPROM for user programs

Kind of terminals

screw terminals

Mounting

wall or panel mounted (cut out 138(w)x92(h) mm)

Number of heating circuits

1

Housing (HxWxD)

96 mm | 114 mm | 105 mm

Max. ambient temperature

50 oC

 

Additional description

Features:

 

 

 

 

 

  • Self adaptive heating curve
  • Optimum start/stop operation with remote room sensor
  • Holiday programme
  • Automatic summer/winter operation switch

    Aquatrol 2000

    Model Number

    Description

     

     

    Features

    W6060C1067

    Controls first boiler and second boiler in sequence

     

     

    Optimum start

    Boiler lead lag change over

    Pump & valve exercise

     Accessories

  • Outside temperature sensor                        T7043E1008
  • Strap-on flow water temperature sensor        T7044C1002
  • Immersion flow water temperature sensor
  •     T7043F1006
  • Room units (space temperature sensor        T8102B1001
  • Wall mount sub base                                 K42007745-005