MAMAC - Electropneumatic Transducers

-
No air consumption
-
100% solid state piezoresistive silicon pressure sensor
-
High air flow capacity
-
Field selectable 4-20 mA, 0-5 VDC or 0-10 VDC input
-
Universal 24 VAC/VDC supply voltage
-
Short circuit and reverse polarity protected inputs and outputs
-
Auto/manual switch with separate increase/Decrease pushbuttons (EP-313)
-
Precision pressure gauge for branch line indication
-
Non-interactive zero and span trimmers
-
Smallest size in the industry
-
Conforms to EMC standards EN50082-1/ EN55014/EN60730-1
The EP-311/313 incorporates a quiet low-wattage poppet valve and
pressure sensor to measure and adjust the branch line pressure
proportional to the input. This unit has no air consumption and is
immune to mounting orientation or supply line pressure fluctuations.
The EP-313 incorporates a manual override switch and, in the manual
mode, the pressure can be increased or decreased with two pushbutton
switches. This feature is most desirable for check out/commissioning
and manual operation in case of controller failure. Universal 24
VAC/24 VDC supply voltage and field selectable 4-20mA, 0-5 VDC, or
0-10 VDC inputs ensures single unit compatibility to most of the
systems. Unique steel chassis design substantially reduces the
overall size of the unit and, at the same time, provides for ease of
installation in a control panel directly or with a snap track. A
precision gauge is provided for the branch line pressure. Rugged
aluminium manifold, brass barb fittings, floating poppet solenoid
valves, silicon pressure sensor, high performance electronics and a
liberal two year warranty are some of the features which make the
EP-311/313 the highest performance and the most reliable
electropneumatic transducer in the industry.
SPECIFICATIONS:
|
Accuracy*:
±
1% FS
Maximum Supply Pressure:
40 psig
Pressure Differential:
(Supply to Branch) 0.1 psig
Supply Voltage:
18-28 VAC/VDC
Supply Current:
150 mA
Enclosure:
18 Ga C. R. Steel Chassis
Finish:
Baked on enamel-PMS2GR88B
Compensated Temp Range:
25°F-150°F (4°C-65°C)
Conformance:
EMC Standards EN50082-1(1992) EN55014(1993)/EN60730-1(1992)
*Includes non-linearity, hysteresis and non-repeatability |
T. C. Error:
±0.025%/°F
(.03%/°C)
Media Compatibility:
Clean dry air or any inert gas
Port Connection:
1/4"OD poly tubing
Environmental:10-90%RH
Non-Condensing
Termination:
Screw terminal block
Wire Size:
12 Ga max.
Input Impedance:
301 ohms (4-20 mA)
10K ohms (0-5/0-10 VDC)
Weight:
1.0 lbs. (.45 kg)
|
ORDERING INFORMATION: EP-

|
311
(without)
313
(with) |
315
(3-15 psig)
020
(0-20 psig)
|
Example: EP-313-020:
With manual override and 0-20 psig range.
CAUTION: Do not use on oxygen service, in explosive/hazardous environment or with flammable/combustible media.
The EP-311/313 incorporate a novel concept to convert an analogue
signal into proportional pneumatic pressure. This concept was first
introduced in the early 1980s by Mamac Systems, Inc. and refined
over the years. Unlike other units
which bleed/consume air to maintain pressure, our design utilizes a
100% solid state precision piezoresistive silicon pressure sensor to
measure the pneumatic branch line pressure. This signal is utilized
by sophisticated integrated circuits to compare the branch line
pressure to the input and energize two independent solenoid valves
to increase or decrease the branch line pressure while constantly
monitoring the change. In this way, the EP-311/313 can provide a
proportional pressure change to the analog input without air
consumption and with zero pressure differential between main air
supply and the branch output. The electronic circuit measures the
rate of pressure change in the branch line and manipulates the
respective solenoid valve in a predictive fashion to achieve the
desired result without over-correcting or "hunting".
The EP-313 has an additional manual override feature. The unit can
be switched to the manual mode and the branch line pressure can be
increased or decreased by two independent push-button switches. This
feature is most desirable for checkout/commissioning or manual
operation of the pneumatic actuator. When switched back to the
automatic mode, the unit will immediately start tracking the
analogue signal. For critical applications in which control downtime
is not allowable, the manual mode can be utilized to operate the
system during maintenance or controller failure.
The EP-311/313 incorporates sophisticated circuits to provide field
selectable 4-20 mA, 0-5 VDC or 0-10 VDC input flexibility. With
fixed input units, in case of engineering error or incorrect
selection, the only solution is expensive product exchange or
replacement. Similarly, numerous units must be kept in stock as
spares to cover all input requirements in case of field failure. The
EP-311/313 with the field selectable input feature, eliminates above
mentioned costly inefficiencies. A single unit can be configured to
cover all input requirements in a particular application thereby
eliminating any possibility of incorrect input selection.
Additionally, one unit can be kept in stock and, in the event of a
failure, it can be field configured thereby eliminating the need to
stock numerous fixed input units.
Universal unregulated 24 VAC/VDC supply voltage feature further
enhances the flexibility of the EP– 311/313 transducer. This feature
eliminates specialized power supply requirement for the
electro-pneumatic transducer thereby significantly reducing labour,
engineering, and power supply costs. Similarly, in retrofit
applications regardless of the supply voltage present, the
EP-311/313 can be engineered into the application without making
expensive changes. The unit is protected against supply voltage
reverse polarity and input-to-ground short circuit.
The EP-311/313 utilizes a solid aluminium manifold, poppet solenoid
valves, and rugged o-ring sealed brass fittings to provide long
term, reliable, leak-proof performance. A precision pressure gauge
is also mounted directly onto the manifold for branch line pressure
indication. Unique steel chassis design substantially reduces the
overall size of the unit and, at the same time provides for ease of
installation in a control panel directly or with a snap track.
Easily accessible wire termination, manual operation switches, zero
and span trimmers, input configuration shorting plugs for field
selection, and LED indication are some of the features which not
only reduce the installation and start-up time, but also ensure ease
of operation. If the
control system design requires that the unit bleeds down to zero
pressure in case of power failure, Mamac Systems, Inc. offers a
EP-350 failsafe module. Up to four transducers can be attached to
one EP-350 and if the fail-safe module detects a loss of supply
voltage, it will bleed all four transducers to zero pressure. This
combination offers unparalleled flexibility to have fail-safe
operation for only those control loops which require it.
Automated NIST traceable pressure controllers and precision pressure
sensors are utilized to calibrate and certify the EP-311/313.
Calibration data on each unit is archived digitally for SPC and QC
purposes. All automated calibration systems are networked and data
is available on-line to numerous individuals at the same time. In
this way, extremely high standards of quality and calibration
integrity are maintained.