MAMAC - Humidity & Temperature Transducers
· Ultra-fast
response polymer capacitance humidity sensor and
precision thermistor or platinum RTD Temperature
Sensor
· Not
affected by condensation, fog, high humidity or
contaminants
· Highly
accurate, repeatable, stable output with
negligible hysteresis
· Wide
12-40 VDC/12-35 VAC unregulated supply voltage
(humidity only)
· Two
temperature compensated humidity output
versions, 4-20 mA 2-wire or field selectable 0-5
VDC/ 0-10 VDC
· NIST
traceable ± 2% or ± 3% calibration and ±0.2%°C
thermistor interchangeability or ± 0.1% RTD
accuracy
· Enclosure
type NEMA 4 (IP-65) duct mount
· Conforms
to EMC standards EN50082-1/ EN55014/EN60730-1
The HU-226 is an extremely fast, stable and accurate Temp/Humidity Transducer designed for harsh environments. The polymer humidity capacitance sensor is not affected by harsh contaminants, condensation, fog or extremely high humidity over a prolonged period of time. If dust or other contaminants accumulate on the sensor, the probe can be washed in industrial grade isopropyl alcohol and put back in service without any calibration shift. Each unit is individually calibrated in an environmental test chamber to meet or exceed NIST traceable ± 2% or ± 3% accuracies. The HU-226 is temperature compensated for -30°F to +130°F operation with negligible error. Field selectable outputs, and fully temperature compensated NIST traceable accuracy, non-interacting zero and span adjustments, NEMA 4 (IP-65) steel enclosure with external mounting bracket, short circuit and reverse polarity protected output, and a liberal two year warranty are some of the features which make the HU-226 the industry's highest performance, most reliable Temp/Humidity Transducer.
SPECIFICATIONS:
|
HUMIDITY TRANSDUCER
Accuracy*:
±2% / ±3% RH
Range:
0-100% RH
Hysteresis:
±1%
Supply voltage:
12-40 VDC 12-35 VAC (VDC output units only)
Compensated Temp Range:
-30°F-130°F (-35°C-55°C)
Load Impedance:
3000 ohms max. at 40 VDC (mA output unit 1000 ohms min. (VDC
output unit)
TEMPERATURE SENSOR
Interchangeability:
±0.2°C
Heat Dissipation:
3.0 mW/°C
R/T Characteristics:
See TI. SN01-01
Operating Temp.:
-30°F to 130°F (-35°C to 55°C)
Conformance:
EMC Standards EN50082-1 (1992)
EN55014 (1993)/EN60730-1 (1992)
* Includes non-linearity and non-repeatability
|
PLATINUM RTD SENSOR
Accuracy:
0.12% at 0°C
Resistance:
100 or 1000 ohm at 0°C
Standard:
Din 43760
Operating Temp. Range:
-30°F to 130°F (-35°C to 55°C)
Heat Dissipation:
3.0 mW/°C
Technology:
Thin film deposition laser trimmed
(LPVD)
Conformance:
EMC Standards EN50082-1(1992)
EN55014 (1993)/EN60730-1 (1992)
GENERAL SPECIFICATIONS
Environmental:
10-90% RH Non-Condensing
Enclosure:
18 Ga C.R. Steel NEMA 4 (IP-65)
Finish:
Baked on enamel -PMS2GR88B
Termination:
Unpluggable screw terminal block
Wire Size:
12 Ga maximum
Weight:
Duct mount 1.0 lbs. (.45 kg) |
ORDERING INFORMATION: HU-

|
± 2%
± 3% ‡ with 11k OHM resistor in parallel |
mA
(4-20 mA 2-wire)
VDC
(0-5 VDC or 0-10 VDC field selectable) |
3
1,000 ohm Platinum R/T Table #3
5
1000 ohm Balco Table #5
7
10,000 ohm Thermistor at 25°C R/T Table #7
7Z‡
10,000 ohm Thermistor at 25°C Table #7Z
10
3,000 ohm Thermistor at 25°C Table #10
12
10,000 ohm Thermistor at 25°C Table #12
17
20,000 ohm Thermistor at 25°C Table #17 |
Example:
HU-226-2-mA-3: Temperature/Humidity
Transducer, ±2%RH accuracy with 4-20 mA output. See Table 3, 1000
ohm Platinum R/T Temperature Sensor.
The HU-226 incorporates a bulk polymer capacitive
humidity sensor and precision NTC thermistor/platinum RTD
temperature sensor. Both Temperature and Humidity Sensors are immune
to most contaminants and at the same time provide a stable,
repeatable, accurate humidity and temperature measurement with
negligible hysteresis. The sensing elements are not affected by
condensation. In fact, the probe may be immersed in distilled water
without degrading the calibration accuracy. The HU-226 utilizes
sophisticated integrated circuits to provide a high level, fully
conditioned, and temperature compensated humidity output. The
thermistor temperature sensors are available with more than ten
different industry standard resistance to temperature curves
offering compatibility to most if not all control systems. All
thermistor sensors offer ±0.2°C interchangeability/accuracy. All
thermistors strictly conform to industry standard R/T curves. The
platinum RTD’s are available with 100 ohm or 1000 ohm din 437630
standards with glass beaker ±0.12% accuracy at 0°C. All temperature
sensors have more than 3.0 mW / °C heat dissipation constant.
On VDC output units (humidity only), two additional field selectable
options are available; dual outputs 0-5 or 0-10 VDC, and dual
unregulated supply voltages 12-35 VAC or 12-40 VDC. By merely moving
a shorting plug, one can select the desired output for the specific
application. As far as supply voltage is concerned, the unit
automatically configures for AC or DC and no field selection is
necessary. Another feature is that the output is fully protected
from short circuit to ground, or if the supply voltage is applied by
mistake to the output. Past experience demonstrates that field
related wiring problems do occur. Instead of denying this fact, this
protection circuit is designed in to ensure trouble-free start-up.
The VDC output unit is also designed to handle low impedance
circuits. In fact, the unit can drive up to 1K ohm minimum. In this
way, multiple controllers, indicators, or other devices can be
paralleled to the output without performance degradation.
The mA output units (humidity only) function over a wide unregulated
supply voltage range: 12-40 VDC without any effect on calibration or
performance. The unit has reverse polarity protection built in. As a
result, it is next to impossible to damage the unit by wiring
incorrectly.
By using sophisticated low dropout voltage regulators and CMOS
integrated circuits, the mA output unit can drive very high output
impedance. In fact, with only 12 VDC supply, the unit can drive 400
ohms. At 40 VDC, the unit is capable of handling up to a 3000 ohm
load. In this way, the output loop can be tied in series to multiple
controllers, indicators, and other devices without degrading the
performance.
NIST traceable humidity standards are utilized to calibrate and
certify the HU-226. Calibration data on each unit is archived
digitally for SPC and QC purposes. All automated calibration systems
are networked and data is available on line to numerous individuals
at the same time. In this way, extremely high standards of quality
and calibration integrity are maintained.
The HU-226 incorporates a rugged NEMA 4 (IP-65) fully gasketed, dust
proof and splash proof enclosure. The enclosure has an external
mounting bracket to facilitate field installation. A 1/2'' (.875''
/22.25 mm diameter) knock-out for conduit connection is also
provided. A liquid tight cable connector is supplied if the unit is
not being hard wired. Once installed, the enclosure maintains its
environmental rating and protects the electronics and the sensing
element from condensation, corrosive contaminant’s and other
environmental pollutants. The enclosure also has additional features
for ease of installation including unpluggable terminal block,
easily accessible zero and span trimmers, and conveniently located
shorting plugs for field selection.