MAMAC - Pneumatic Pressure Transducers
-
100% solid state fused piezoresistive silicon sensing element
-
Rugged, manifold assembly
-
Up to 40 psig maximum pressure
Up to 3 field selectable ranges in a
single unit
Wide 12-40 VDC/12-35 VAC unregulated
supply voltage
Two temperature compensated output
versions, 4-20 mA 2-wire or field selectable
0-5 VDC/ 0-10 VDC
NIST traceable calibration
Rugged NEMA 4 (IP-65) enclosure with
external mounting bracket
Short circuit and reverse polarity
protected
Conforms to EMC standards EN50082- 1/
EN55014/EN60730-1
The PR-243 incorporates sophisticated integrated circuits and a 100%
solid state piezoresistive silicon sensor to not only provide a
high-level, fully-conditioned and temperature compensated output,
but also to offer up to three (3) field selectable pressure ranges
in one unit. The field selectable feature eliminates costly
inefficiencies by providing a single unit which can be configured to
cover all the pressure ranges for a particular application. For
instance, 5, 10 and 20 psig in one unit. Two industry standard
output versions are available, 4-20mA 2-wire loop or field
selectable 0-5 VDC/0-10 VDC. Wide 12-40 VDC or 12-35 VAC unregulated
supply voltage and a broad 0 o F - 180 o F compensated temperature
range ensures compatibility mounting bracket, fully temperature
compensated NIST traceable accuracy and a liberal two year warranty
are some of the features which make the PR-243 the industry’s most
reliable, rugged, and economical pressure transducer.
SPECIFICATIONS:
|
ACCURACY*:
± 1% FS
Maximum Pressure:
40 psig
Supply Voltage:
12-40 VDC 12-35 VAC (VDC output units only)
Supply Current:
VDC Units - 10 mA
max.mA Units - 20 mA max.
Enclosure:
18 Ga C. R. Steel NEMA 4 (IP-65)
Finish:
Baked on enamel-PMS2GR88B
Conformance:
EMC Standards EN50082- 1(1992)
EN55014(1993)/EN60730- 1(1992)
*Includes non-linearity, hysteresis and non
repeatability
|
Compensated Temp Range:
0 °F -180 °F (-18 °C-82 °C)
T. C. Error:
±0.025%/° F (.03%/°C)
Media Compatibility:
Dry Air or Inert Gases
Port Connection:
1/4” Brass Hose Barb
Environmental:10-90%RH Non-Condensing
Termination:
Unpluggable screw terminal block
Wire Size:
12 Ga max.
Load Impedance:3K ohms max. at 40 VDC (mA output units) 1K ohms
min. (VDC output units)
Weight:
1.0 lbs. (.45 kg)
|
ORDERING INFORMATION: PR-243

|
R1 (psig) 0 TO 20 / 0 TO 10 / 0 TO 5 mA (4-20 mA 2-wire)R2 (psig) 0 TO 30 / 0 TO 15 / 0 TO 7.5 VDC (0-5 VDC or 0-10 VDC field selectable)R3 (psig) 3 TO 15R4 (kPa) 0 TO 140 / 0 TO 70 / 0 TO 35R5 (kPa) 0 TO 200 / 0 TO 100 / 0 TO 50R6 (kPa) 20 TO 100 |
mA
(4-20 mA 2-wire)
VDC
(0-5 VDC or 0-10 VDC field selectable)
|
CAUTION: Do not use on oxygen service, in explosive/hazardous environment or with flammable/combustible media.
The PR-243
sensing element is a 100% solid state piezoresistive silicon
chip featuring low hysteresis, excellent repeatability, and
long term stability. The chip is connected as a four active
element bridge circuit for optimum linearity and
sensitivity. Signal conditioning and temperature
compensation are performed by industrial quality,
state-of-the-art integrated circuits to provide an accurate,
linear, and high level output that requires no additional
signal conditioning.
The PR-243 incorporates
sophisticated integrated circuits to not only provide a high
level, fully conditioned and temperature compensated output,
but also to offer field selectable flexibility which was
unheard of in the industry. The PR-243 offers up to three
field selectable pressure
ranges in one unit. In this way, a customer does not
need to know the exact pressure range prior to selection. A
unit can be field configured for the desired pressure range
in the field. With fixed range units, in case of engineering
error or incorrect selection, the only solution is expensive
field recalibration or time consuming product exchange or
replacement. Similarly, numerous units have to be kept in
stock as spares to cover all ranges in case of field
failure. The PR-243 with the field selectable pressure range
feature, eliminates above mentioned costly inefficiencies. A
single unit can be configured to cover all the pressure
ranges in a particular application thereby eliminating any
possibility o incorrect range selection. Additionally, one
unit can be kept in stock and, in the event of a failure, it
can be field configured thereby eliminating the need to
stock numerous fixed range units. (For a complete listing of
all the ranges available, please see the ordering
information section on page three.)
The VDC output unit is also
designed to handle low impedance circuits. In fact, the unit
can drive up to 1K ohms minimum. In this way, multiple
controllers, indicators, or other devices can be paralleled
to the output without performance degradation.
The mA output units can function over a wide unregulated supply voltage range: 12-40 VDC without any effect on calibration or performance. The unit has reverse polarity protection built in. As a result, it is next to impossible to damage the unit by miswiring. By using sophisticated low drop-out voltage regulators and CMOS integrated circuits,
the mA output unit can drive very high output impedance. In fact, with only 12 VDC supply, the unit can drive 400 ohms. At 40 VDC, the unit is capable of handling up to 3000 ohms load. In this way, the output loop can be tied in series to multiple controllers, indicators, and other devices without degrading the performance. Automated NIST traceable pressure controllers and precision pressure sensors are utilized to calibrate and certify the PR-243. Calibration data on each unit is archived digitally for SPC and QC purposes.
All automated calibration systems
are networked and data is available on-line to numerous
individuals at the same time. In this way, extremely high
standards of quality and calibration integrity are
maintained. Each unit is individually temperature
compensated in an environmental chamber. The temperature
compensation data is also digitized and archived for future
reference purposes. Compensating each unit individually
ensures that published specifications are adhered to.
The PR-243 incorporates a rugged
NEMA 4 (IP-65) fully gasketed, dust proof and splash proof
enclosure. The enclosure has an external mounting bracket to
facilitate field installation. A 1/2” (.875"/22.25mm dia.)
knock-out for conduit connection is also provided. A liquid
tight cable connector is also supplied if the unit is not
being hard wired. Once installed, the enclosure maintains
its environmental rating and protects the electronics and
the sensing element from condensation, corrosive
contaminants and other environmental pollutants. The unit
also has additional features for ease of installation
including unpluggable terminal block, easily accessible zero
and span trimmers, and conveniently located shorting plugs
for field selection.