MAMAC - Pressure Transducers
· 100%
solid state, micro-machined, glass-on-silicon,
ultra-stable capacitance sensor
·
· Up
to
300% overpressure without zero shift
· Up to
500% burst pressure
· Up
to
3 field selectable ranges in
single unit
· Wide
12-40 VDC/12-35 VAC unregulated supply voltage
· Two
temperature compensated output versions, 4-20 mA
2-wire or field selectable 0-5 VDC/0-10 VDC
· NIST
traceable calibration
· Rugged NEMA 4 (IP-65)
enclosure with external mounting bracket
· Short
circuit and reverse polarity protected
· Conforms
to EMC standards EN50082-1/EN55014/EN60730-1
The PR-264 incorporates sophisticated integrated circuits and a new
fused silicon monolithic cavity pressure sensor to not only provide
a high-level, fully-conditioned and temperature compensated output,
but also to offer up to three (3) field selectable pressure ranges
in one unit. The field selectable feature eliminates costly
inefficiencies by providing a single unit which can be configured to
cover all the pressure ranges for a particular application. For
instance, 25.0, 50.0 and 100.0 psig in one unit. The 316L stainless
steel monolithic pressure cavity not only provides media
compatibility for most of the applications, but also offers a
leak-proof solution for today's environment conscious customers. Two
industry standard output versions are available, 4-20mA 2-wire loop
or field selectable 0-5 VDC/0-10 VDC or 12-35 VAC unregulated supply
voltage and a broad 0°F-180°F compensated temperature range ensures
compatibility to most of the applications. Rugged NEMA 4 (IP-65)
enclosure, gasketed cover, external mounting bracket, fully
temperature compensated NIST traceable accuracy and a liberal two
year warranty are some of the features which make the PR-264 the
industry's most reliable, rugged, and economical pressure
transducer.
SPECIFICATIONS:
|
ACCURACY*:
± 1% FS Maximum Pressure: 300% Burst Pressure: 500%
Supply Voltage:
12-40 VDC 12-35 VAC (VDC output units only)
Supply Current:
VDC Units - 10 mA max. mA Units - 20 mA max.
Enclosure:
18 Ga C. R. Steel NEMA 4 (IP-65)
Finish:
Baked on enamel-PMS2GR88B
Conformance:
EMC Standards EN50082- 1(1992) EN55014(1993)/EN60730-
1(1992)
*Includes non-linearity, hysteresis and nonrepeatability |
Compensated Temp Range:
0 °F -180 °F (-18 °C-82 °C)
T. C. Error:
±0.025%/° F (.03%/°C) Media Compatibility: Liquid/gases compatible to 316L stainless steel Port Connection: 1/8” NPT
Environmental: 10-90%RH
Non-Condensing
Termination:
Unpluggable screw terminal block
Wire Size:
12 Ga max.
Load Impedance: 3K
ohms max. at 40 VDC (mA output units) 1K ohms min. (VDC
output units)
Weight:
1.0 lbs. (.45 kg) |
ORDERING INFORMATION: PR-264-

|
R1 (psig) 0 TO 100 / 0 TO 50 / 0 TO 25 R2 (psig) 0 TO 300 / 0 TO 150 / 0 TO 75 R3 (psig) 0 TO 500 / 0 TO 250 / 0 TO 125 R4 (kPa) 0 TO 700 / 0 TO 350 / 0 TO 175 R5 (kPa) 0 TO 2000 / 0 TO 1000 / 0 TO 500 R6 (kPa) 0 TO 3500 / 0 TO 1750 / 0 TO 875 |
mA (4-20 mA 2-wire) VDC (0-5 VDC or 0-10 VDC field selectable |
Example: PR-264-R1-mA: With R1
Range which has three(3) field selectable range options and 4-20 mA
output.
CAUTION: Do not use on oxygen service, in explosive/hazardous
environment or with flammable/combustible media.
The PR-264 incorporates sophisticated integrated circuits to not
only provide a high level, fully conditioned and temperature
compensated output, but also to offer field selectable flexibility
which was unheard of in the industry. The PR-264 offers up to three
field selectable pressure ranges in one unit. In this way, a
customer does not need to know the exact pressure range prior to
selection. A unit can be field configured for the desired pressure
range in the field. With fixed range units, in case of engineering
error or incorrect selection, the only solution is expensive field
recalibration or time consuming product exchange or replacement.
Similarly, numerous units have to be kept in stock as spares to
cover all ranges in case of field failure. The PR-264 with the field
selectable pressure range feature, eliminates above mentioned costly
inefficiencies. A single unit can be configured to cover all the
pressure ranges in a particular application thereby eliminating any
possibility of incorrect range selection. Additionally, one unit can
be kept in stock and, in the event of a failure, it can be field
configured thereby eliminating the need to stock numerous fixed
range units. (For a complete listing of all the ranges available,
please see the ordering information section on page three.)
Past experience demonstrates that field
related wiring problems do occur. Instead of denying this fact, the
protection circuit is designed in to ensure trouble-free start-up.
The VDC output unit is also designed to handle low impedance
circuits. In fact, the unit can drive up to 1K ohms minimum. In this
way, multiple controllers, indicators, or other devices can be
paralleled to the output without performance degradation.
The mA output units can function over a wide unregulated supply
voltage range: 12-40 VDC without any effect on calibration or
performance. The unit has reverse polarity protection built in. As a
result, it is next to impossible to damage the unit by mis-wiring.
By using sophisticated low drop-out voltage regulators
and CMOS integrated circuits, the mA output unit can drive
very high output impedance. In fact, with only 12 VDC supply, the
unit can drive 400 ohms. At 40 VDC, the unit is capable of handling
up to 3000 ohms load. In this way, the output loop can be tied in
series to multiple controllers, indicators, and other devices
without degrading the performance.
Automated NIST traceable pressure controllers and precision pressure
sensors are utilized to calibrate and
certify the PR-264. Calibration data on each unit is archived
digitally for SPC and QC purposes. All automated calibration systems
are networked and data is available on-line to numerous individuals
at the same time. In this way, extremely high standards of quality
and calibration integrity are maintained. Each unit is individually
temperature compensated in an environmental chamber. The temperature
compensation data is also digitized and archived for future
reference purposes. Compensating each unit individually ensures that
published specifications are adhered to.
The PR-264 incorporates a rugged NEMA 4
(IP-65) fully gasketed, dust proof and splash proof enclosure. The
enclosure has an external mounting bracket to facilitate field
installation. A 1/2" (.875"/22.25mm dia.) knock-out for conduit
connection is also provided. A liquid tight cable connector is also
supplied if the unit is not being hard wired. Once installed, the
enclosure maintains its environmental rating and protects the
electronics and the sensing element from condensation, corrosive
contaminants and other environmental pollutants. The unit also has
additional features for ease of installation including unpluggable
terminal block, easily accessible zero and span trimmers, and
conveniently located shorting plugs for field
selection.