MAMAC - Sensor Only Enclosure Options
-
Attractive, off-white finish, made from rugged ABS plastic.
-
Three options available
-
Sensor only.
-
Sensor with under-cover RJ11 Communication jack.
-
Sensor, push-button override, sliding setpoint adjust, and RJ11 Communication jack.
-
Custom set point adjust, push-button override, communication jack available, most available in three weeks or less.
-
Mounts on standard 2” X 4” junction box.
-
Rugged two-piece construction, cover secured to sub base via Allen screws.
-
·Select from 12 types of thermistors, platinum, nickel, or Balco RTD's.
TE-205-EX wall sensors provide reliable space temperature sensing.
The rugged enclosure is tamper proof, due to a unique mounting
scheme and Allen screws that secure the cover to the sensor sub
base. Select from 12 types of thermistors, platinum, nickel, or
Balco RTD's. Customization of set-point adjust, push-button
override, communication jack is possible, many available in three
weeks for less. All TE-205-EX wall sensors can be mounted in sheet
rock and are designed to mount on standard 2”X4” junction box. By
depressing the momentary push-button located along the upper right
side of the sensor, after hours comfort control conditions can be
requested by facility occupants. Two types of after hours
temperature override are provided. Refer to individual
manufacturer’s override schemes. Simple, intuitive temperature
control adjustment “slider” provided for occupant temperature
modification.
SPECIFICATIONS:
Platinum RTD sensors:
± 0.1% @ 32.0º F (0.0º C), Alpha: 385 per DIN 43760
Nickel RTD sensors:
± 0.5º F @ 70.0º F (21.1º C), 6,000 PPM/K T.C.R.
Balco RTD sensors:
± 0.5º F @ 70.0º F (21.1º C), 4,300 PPM/K T.C.R.
Thermistor sensors:
±
0.4º F (0.2º C) interchangeability @ 77.0º F (25.0º C)
Operating and Storage Temperatures:
32.0º F to 158.0º F (0.0º C to 70.0º C)
Finish: Tan colour, ABS plastic
ORDERING INFORMATION:
ORDERING EXAMPLES:
After
TE-205-EX,
select sensor order code and option order code. For example, A
TE-205-EX-3-0
is a sensor with 1,000 Ohm platinum RTD and No Option.
*NEED RESISTANCE VERSUS TEMPERATURE TABLES?:
Please refer to publication TI.700.10.
INSTALLATION INSTRUCTIONS:
Inspection -
Inspect the package and device for obvious signs of damage. If
damaged, please notify your shipper or individuals in your
organization responsible for shipping products.
To Get Started -
Tools are not provided. You will need drill, drill bits, or
screwdriver and screws to mount this device. If you mount this
device in sheet rock, you should have appropriate #8 screws and
plastic wall
anchors. If you mount this device to a standard 2”x4” junction box,
you will need two (2) #8 self tapping screws to mount the sub base.
Set the Jumpers -
Turn Allen screws CW on the bottom of the
unit. Remove the cover. Refer to Figure 1 on the top of page three
and make the appropriate jumper setting (TE-205-EX-X-1,-2,-3,-5
only).
NOTE:
Before setting TE205 jumpers, please refer to
control system manufacturer for bypass operation requirements.

Mount the Sub base
- Mount device approximately five (5) feet above floor level. Pull
wires through junction box or through hole in sheet rock through
hole in the back of the sub base. Mount the sub base on the
sheet rock or junction box, observing directions above. Screw down
the sub base.
Terminations
-
Sensor, Bypass, Set point Adjust.
Wire per wiring diagrams (Figure 2-4) below.
Use no larger than 12 AWG wiring. Terminate, complying to wiring
rules by supplier of controller products.